Sauna electrical requirements

What a sauna asks of your electrical panel: the current it draws, and the breaker and wire its maker's manual names. The amps are arithmetic. The rest is quoted from manuals and code text, with the edition, and none of it replaces a licensed electrician.

Sources read 22 Nov 2026How figures are checked
Supply voltage
Current drawn at full power0 A

Share of each breaker size

  1. 15 A
  2. 20 A
  3. 30 A
  4. 40 A
  5. 50 A
  6. 60 A

The share is plain arithmetic: current divided by breaker rating. Whether a share is allowed, and what wire it needs, is set by the heater's manual and your electrical code, quoted below. A licensed electrician decides.

From the manuals

What each heater's manual asks for

A traditional sauna heater is hard-wired. The makers print the current and, in HUUM's case, the breaker and wire for every model. Harvia's and Finnleo's US manuals print the current and wire but no breaker size, so we print none for them.

Current drawn at full power, as each manual or product page prints it. Red: traditional heaters. Blue: infrared cabins. HIVE 12 to 18 are fed by two breakers, as their manual states.
  1. HUUM DROP 4HUUM US manual, 240 V
    18.75 A, 30 A breaker1
  2. HUUM DROP 6HUUM US manual, 240 V
    25 A, 30 A breaker2
  3. HUUM DROP 7HUUM US manual, 240 V
    31.25 A, 40 A breaker3
  4. HUUM DROP 9HUUM US manual, 240 V
    37.5 A, 50 A breaker4
  5. HUUM CLIFF 11HUUM US manual, 240 V
    43.75 A, 50 A breaker5
  6. HUUM HIVE 12HUUM US manual, 240 V
    50 A, two 30 A breakers6
  7. HUUM HIVE 15HUUM US manual, 240 V
    62.5 A, two 50 A breakers7
  8. HUUM HIVE 18HUUM US manual, 240 V
    75 A, two 50 A breakers8
  9. Harvia KIP-30-B1Harvia US manual, 240 V
    12.5 A9
  10. Harvia KIP-45-B1Harvia US manual, 240 V
    18.8 A10
  11. Harvia KIP-60-B1Harvia US manual, 240 V
    25 A11
  12. Harvia KIP-80-B1Harvia US manual, 240 V
    33.3 A12
  13. Health Mate Enrich 2Infrared cabin, 120 V
    120 V at 1,780 W and 15 A17
  14. JNH Tosi 2Infrared cabin, 120 V
    120 V at 15 A and 1,540 W18
  15. Sunlighten Amplify IIInfrared cabin, 120 V
    120 V at 1,880 W and 15.67 A19
  16. Clearlight Sanctuary 2Infrared cabin, 120 V
    120 V at 2,260 W and 18.83 A20
HUUM (current US manuals): current, breaker and wire
ModelPowerCurrentBreakerWire
HUUM DROP 44.5 kWManufacturer manualChecked 22 Nov 2026HUUM DROP US installation and operation manual (H1001L08 v8), Table 2 (240 V)Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.Re-check by 22 Nov 2027Full ledger18.75 A30 A breaker10 AWG
HUUM DROP 66 kWManufacturer manualChecked 22 Nov 2026HUUM DROP US installation and operation manual (H1001L08 v8), Table 2 (240 V)Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.Re-check by 22 Nov 2027Full ledger25 A30 A breaker10 AWG
HUUM DROP 77.5 kWManufacturer manualChecked 22 Nov 2026HUUM DROP US installation and operation manual (H1001L08 v8), Table 2 (240 V)Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.Re-check by 22 Nov 2027Full ledger31.25 A40 A breaker8 AWG
HUUM DROP 99 kWManufacturer manualChecked 22 Nov 2026HUUM DROP US installation and operation manual (H1001L08 v8), Table 2 (240 V)Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.Re-check by 22 Nov 2027Full ledger37.5 A50 A breaker8 AWG
HUUM CLIFF 1111.0 kWManufacturer manualChecked 22 Nov 2026HUUM CLIFF US user manual (H1004L03 v9), Table 1 (240 V)Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.Re-check by 22 Nov 2027Full ledger43.75 A50 A breaker8 AWG
HUUM HIVE 1212 kWManufacturer manualChecked 22 Nov 2026HUUM HIVE US user manual (H1002L03 v13), Table 1 (240 V)Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.Re-check by 22 Nov 2027Full ledger50 Atwo 30 A breakerstwo 10 AWG
HUUM HIVE 1515 kWManufacturer manualChecked 22 Nov 2026HUUM HIVE US user manual (H1002L03 v13), Table 1 (240 V)Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.Re-check by 22 Nov 2027Full ledger62.5 Atwo 50 A breakerstwo 6 AWG
HUUM HIVE 1818 kWManufacturer manualChecked 22 Nov 2026HUUM HIVE US user manual (H1002L03 v13), Table 1 (240 V)Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.Re-check by 22 Nov 2027Full ledger75 Atwo 50 A breakerstwo 6 AWG
Harvia KIP (US manual): current and cable. No breaker size is printed.
ModelPowerCurrentCable
Harvia KIP-30-B13 kWManufacturer manualChecked 22 Nov 2026Harvia KIP (built-in controls) instructions for installation and use, 5.3 SpecificationsThe manual gives current and cable size but no breaker rating; the electrician sizes the breaker to code.Re-check by 22 Nov 2027Full ledger12.5 A12/2 cable
Harvia KIP-45-B14.5 kWManufacturer manualChecked 22 Nov 2026Harvia KIP (built-in controls) instructions for installation and use, 5.3 SpecificationsThe manual gives current and cable size but no breaker rating; the electrician sizes the breaker to code.Re-check by 22 Nov 2027Full ledger18.8 A10/2 cable
Harvia KIP-60-B16 kWManufacturer manualChecked 22 Nov 2026Harvia KIP (built-in controls) instructions for installation and use, 5.3 SpecificationsThe manual gives current and cable size but no breaker rating; the electrician sizes the breaker to code.Re-check by 22 Nov 2027Full ledger25 A10/2 cable
Harvia KIP-80-B18 kWManufacturer manualChecked 22 Nov 2026Harvia KIP (built-in controls) instructions for installation and use, 5.3 SpecificationsThe manual gives current and cable size but no breaker rating; the electrician sizes the breaker to code.Re-check by 22 Nov 2027Full ledger33.3 A8/2 cable

Harvia's US product page for the KIP60B gives one more line: Harvia KIP60B: fuse min. 25 A at 240 V single phase, 10 AWG supply cable, 169 to 300 cu ftManufacturer pageChecked 22 Nov 2026Harvia US product page, KIP60B 6 kW 240VAC Steel UL (JC60B2401), technical dataA minimum fuse rating, not a full circuit specification; local code and the electrician decide the final breaker.Re-check by 22 May 2027Full ledger.

Finnleo Designer (US manual): current and wire
ModelPowerCurrentWire
Finnleo Designer 4.54.5 kWManufacturer manualChecked 22 Nov 2026Finnleo Designer SL2 heater installation and operating instructions (72-0130), Diagram 2Minimum volume is quoted at a 74 inch wall height and maximum at 96 inches; the chart gives no breaker size.Re-check by 22 Nov 2027Full ledger18.8 A10 AWG
Finnleo Designer 6.06.0 kWManufacturer manualChecked 22 Nov 2026Finnleo Designer SL2 heater installation and operating instructions (72-0130), Diagram 2Minimum volume is quoted at a 74 inch wall height and maximum at 96 inches; the chart gives no breaker size.Re-check by 22 Nov 2027Full ledger25 A10 AWG
Finnleo Designer 8.08.0 kWManufacturer manualChecked 22 Nov 2026Finnleo Designer SL2 heater installation and operating instructions (72-0130), Diagram 2Minimum volume is quoted at a 74 inch wall height and maximum at 96 inches; the chart gives no breaker size.Re-check by 22 Nov 2027Full ledger33.3 A8 AWG

What the code text says

We print a code rule only where we read its words. Codes are adopted, and amended, by each state, province or town, so ask your inspector which edition applies to you.

  • NEC 2020, 424.4(B). For fixed electric space-heating equipment, branch-circuit conductors sized not smaller than 125 percent of the loadStandardChecked 22 Nov 2026NFPA 70 National Electrical Code 2020, section 424.4(B), as reprinted in the 2022 California Electrical CodeArticle 424 does not name sauna heaters, so whether this rule applies to a sauna heater is for the local inspector; the rule covers conductors only, and later NEC editions renumber it.Re-check by 22 Nov 2027Full ledger. Article 424 does not use the word sauna; your inspector decides whether it covers your heater. If it does, a heater drawing 25 A would need conductors for 31.25 A (our arithmetic).
  • NEC 2020, 210.20(A). Where a load is continuous, the breaker is overcurrent device rated not less than the noncontinuous load plus 125 percent of the continuous loadStandardChecked 22 Nov 2026NFPA 70 National Electrical Code 2020, section 210.20(A), as reprinted in the 2022 California Electrical CodeThe rule applies to continuous loads; the code text read here does not say a sauna heater is one, and an assembly listed for 100 percent operation is exempt.Re-check by 22 Nov 2027Full ledger. The text we read does not say whether a sauna heater counts as continuous.
  • IRC 2024, M1902.2. Sauna heaters are installed per the manufacturer's instructions and compliant with UL 875StandardChecked 22 Nov 2026ICC International Residential Code 2024, section M1902.2Applies only where this IRC edition is adopted; it does not name a certification body.Re-check by 22 Nov 2027Full ledger. UL 875 covers dry-bath heaters rated 600 V or less, supplied with an automatic temperature control, a manual-reset limit control and a timerStandardChecked 22 Nov 2026UL 875 Ed. 10-2024, Electric Dry-Bath Heaters, scope clause 1.1 on the ANSI Webstore listingThe scope says what a listed heater must include; it does not give the timer length or temperature limits, which sit in the paid standard.Re-check by 22 Nov 2027Full ledger.
  • IRC 2024, M1902.4. A thermostat limiting room temperature to not greater than 194°F (90°C), with a separate sensor within 6 inches (152 mm) of the ceilingStandardChecked 22 Nov 2026ICC International Residential Code 2024, section M1902.4A model code: it applies only where a jurisdiction has adopted this IRC edition, possibly with local amendments, and the 6 inch rule applies only to a sensor not built into the heater.Re-check by 22 Nov 2027Full ledger.
  • Ontario. The Electrical Safety Authority summarises Rule 62-222 as a timed cut-off switch with a maximum setting of 1 hour and no overrideRegulatorChecked 22 Nov 2026Electrical Safety Authority and Ontario Fire Marshal, Flash 25-20-FL, May 2025This is ESA's summary of Ontario Electrical Safety Code Rule 62-222, not the code text, and Ontario's code can differ from the CSA C22.1 code adopted elsewhere in Canada.Re-check by 22 Nov 2027Full ledger, and Rule 62-112 as adjacent combustible materials not subjected to temperatures above 90° CRegulatorChecked 22 Nov 2026Electrical Safety Authority and Ontario Fire Marshal, Flash 25-20-FL, May 2025ESA's summary of a general heating rule in the Ontario code, not the code text, and not a sauna room air temperature limit.Re-check by 22 Nov 2027Full ledger. We did not find the CSA C22.1 text itself in a free source.

GFCI: the makers and the codes may not agree

HUUM and Harvia say not to put the heater on a GFCI breaker. Finnleo says one is not required by the NEC and may nuisance trip:

We have not read a code text that requires a GFCI on a sauna heater, and we have not read one that rules it out. We do not settle this: ask your inspector before the circuit goes in, because a nuisance-tripping breaker and a failed inspection both cost a return visit.

Infrared cabins on 120 V

Sellers say: Plugs into a standard household outlet, no electrician needed Our verdict is Mixed. One seller's guide says most small cabins run on a standard 120 V, 15 A outlet, with larger models on a dedicated 20 A circuitSeller pageChecked 22 Nov 2026Heavenly Heat guide to plug-in infrared saunasOne seller describing the category, not a nameplate. The page gives three wattage ranges that do not agree with each other.Re-check by 22 May 2027Full ledger. The cabins in the chart above say more:

Infrared cabins: power, current and the circuit the maker asks for
ModelSupply, power and currentCircuit
Health Mate Enrich 2120 V at 1,780 W and 15 AManufacturer pageChecked 22 Nov 2026Health Mate, Enrich 2 product page, Electrical and DimensionsThe heater and warranty details come from other sections of the same page, and lifetime coverage applies only to the heater core, harness and wiring.Re-check by 22 May 2027Full ledgerstandard 15 A outlet (NEMA 5-15P)
JNH Tosi 2120 V at 15 A and 1,540 WManufacturer pageChecked 22 Nov 2026JNH Lifestyles, Tosi 2 product page, Technical SpecificationsThe heater counts and warranty come from other sections of the same page.Re-check by 22 May 2027Full ledgerstandard household outlet
Sunlighten Amplify II120 V at 1,880 W and 15.67 AManufacturer pageChecked 22 Nov 2026Sunlighten US shop, Amplify II product page, Specifications and dimensionsThe warranty carries an asterisk for terms we did not capture, and the ETL wording is a brand-wide FAQ statement. Sunlighten's own spec sheet PDF gives a higher rating for the Amplify II, so the two Sunlighten documents disagree.Re-check by 22 May 2027Full ledgerdedicated 20 A circuit
Clearlight Sanctuary 2120 V at 2,260 W and 18.83 AManufacturer pageChecked 22 Nov 2026Clearlight (infraredsauna.com), Sanctuary 2 product page, SpecificationsThe page shows no price, and the dimensions and heater list are in other sections of the same page.Re-check by 22 May 2027Full ledger120 V 20 A outlet (NEMA 5-20P)

Check the arithmetic yourself: 1,880 W divided by 120 V is 15.67 A, which is more than a 15 A circuit carries. That is why the maker asks for a dedicated 20 A circuit. Sunlighten's own spec sheet rates the same cabin higher, at 2270 WManufacturer manualChecked 22 Nov 2026Sunlighten Amplify II spec sheet (Doc 09142026)Read from a two-column PDF as text, so carton and panel sizes run into the same lines; the sheet gives no per-heater wattage.Re-check by 22 May 2027Full ledger, so its two documents disagree: go by the nameplate on the cabin you receive.

Who does the work

Every heater manual we read says a licensed electrician connects it: HUUM: electrical work must be carried out by a licensed electricianManufacturer manualChecked 22 Nov 2026HUUM DROP US manual (H1001L08 v8), page 3The manual later says "certified electrician" for connecting power; it does not define either term.Re-check by 22 Nov 2027Full ledger; Harvia Cilindro manual: connect only by an authorised, licensed professional electrician, with 90 °C copper wire inside sauna wallsManufacturer manualChecked 22 Nov 2026Harvia Cilindro Owner's / Operator's Manual USA, 3.5 Electrical ConnectionsThe 90 °C wire rule is in a later sentence of the same section.Re-check by 22 Nov 2027Full ledger; Finnleo: electrical installation must be made by a licensed electrician under the NEC and local rulesManufacturer manualChecked 22 Nov 2026Finnleo Designer SL2 heater installation and operating instructions (72-0130), Section 4 Electrical hook-upStates who installs, not what the circuit must be.Re-check by 22 Nov 2027Full ledger. HUUM ties its warranty to it: HUUM warranty: applies only if a licensed, professional electrician installed and connected the heater and proof is given to HUUMManufacturer pageChecked 22 Nov 2026HUUM Limited Warranty Terms and Conditions v4 (linked from huumsauna.com/warranty)Does not say what form of proof HUUM accepts.Re-check by 22 May 2027Full ledger.

Next: size the heater for your room, then see what the whole sauna costs.

AUDIT TRAILManuals, code text and spec pages used here37 primary records · Checked 22 Nov 2026
  1. HUUM DROP 4: power, room volume and circuit (240 V)
    HUUM DROP US installation and operation manual (H1001L08 v8), Table 2 (240 V). Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "106-248 ft3 DROP 4 4.5 3–7 m3 18.75 30 10"
    Limit: Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.
  2. HUUM DROP 6: power, room volume and circuit (240 V)
    HUUM DROP US installation and operation manual (H1001L08 v8), Table 2 (240 V). Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "177-318 ft3 DROP 6 6 5–9 m3 25 30 10"
    Limit: Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.
  3. HUUM DROP 7: power, room volume and circuit (240 V)
    HUUM DROP US installation and operation manual (H1001L08 v8), Table 2 (240 V). Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "248-389 ft3 DROP 7 7.5 7–11 m3 31.25 40 8"
    Limit: Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.
  4. HUUM DROP 9: power, room volume and circuit (240 V)
    HUUM DROP US installation and operation manual (H1001L08 v8), Table 2 (240 V). Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "283-460 ft3 DROP 9 9 8–13 m3 37.5 50 8"
    Limit: Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.
    Another source disagrees: DROP 9: 9 kW for 282 to 530 cu ft (8 to 15 m³), 50 A breaker, 6 AWG. Older HUUM DROP manual PDF hosted on a retailer Shopify CDN (shop 21798295), Tables 1 and 2.
  5. HUUM CLIFF 11: power, room volume and circuit (240 V)
    HUUM CLIFF US user manual (H1004L03 v9), Table 1 (240 V). Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "354-566 ft3 CLIFF 11 11.0 43.75 50 8 10-16 m3"
    Limit: Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.
  6. HUUM HIVE 12: power, room volume and circuit (240 V)
    HUUM HIVE US user manual (H1002L03 v13), Table 1 (240 V). Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "424-636 ft3 HIVE 12 12 50 30 + 30 10 + 10 12-18 m3"
    Limit: Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.
  7. HUUM HIVE 15: power, room volume and circuit (240 V)
    HUUM HIVE US user manual (H1002L03 v13), Table 1 (240 V). Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "530-813 ft3 HIVE 15 15 62.5 50 + 50 6+6 15-23 m3"
    Limit: Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.
  8. HUUM HIVE 18: power, room volume and circuit (240 V)
    HUUM HIVE US user manual (H1002L03 v13), Table 1 (240 V). Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "636-989 ft3 HIVE 18 18 75 50 + 50 6+6 18-28 m3"
    Limit: Room range assumes insulated walls; add the maker's cold-surface volume first, and the electrician sizes the circuit to local code.
  9. Harvia KIP KIP-30-B1: power, room volume and supply (240 V)
    Harvia KIP (built-in controls) instructions for installation and use, 5.3 Specifications. Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "KIP-30-B1/B3 KIP-45-B1/B3 KIP-60-B1/B3 KIP-80-B1/B3 Power (kW) 3.0 4.5 6.0 8.0 240 V 1 Phase (B1) Operating voltage 208 V 3 Phase (B3) Frequency (Hz) 50 / 60 12.5 (B1) 18.8 (B1) 25.0 (B1) 33.3 (B1) Current (A) 8.3 (B3) 12.5 (B3) 16.7 (B3) 22.2 (B3) 12/2 (B1) 10/2 (B1) 10/2 (B1) 8/2 (B1) Cable size 14/3 (B3) 14/3 (B3) 12/3 (B3) 10/3 (B3) Storage temperature 0-50°C / 32-122°F SAUNA STONES Size of stones Ø 5-10 cm / 2-4” Quantity of stones 20 kg / 44 lbs SAUNA ROOM 1900 mm / 75’’ (USA) Room height, min. 1980 mm / 78’’ (Canada) Floor area, min. 1 m2 / 10 ft2 1.5 m2 / 16 ft2 2.6 m2 / 28 ft2 3.7 m2 / 40 ft2 Floor area, max. 2 m2 / 20 ft2 2.8 m2 / 30 ft2 3.7 m2 / 40 ft2 6 m2 / 65 ft2 Room volume, min. 2.4 m3 / 84 ft3 2.8 m3 / 100 ft3 4.8 m3 / 170 ft3 7.1 m3 / 250 ft3 Room volume, max. 3.7 m3 / 130 ft3 6 m3 / 210 ft3 8.5 m3 / 300 ft3 12 m3 / 425 ft3"
    Limit: The manual gives current and cable size but no breaker rating; the electrician sizes the breaker to code.
  10. Harvia KIP KIP-45-B1: power, room volume and supply (240 V)
    Harvia KIP (built-in controls) instructions for installation and use, 5.3 Specifications. Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "KIP-30-B1/B3 KIP-45-B1/B3 KIP-60-B1/B3 KIP-80-B1/B3 Power (kW) 3.0 4.5 6.0 8.0 240 V 1 Phase (B1) Operating voltage 208 V 3 Phase (B3) Frequency (Hz) 50 / 60 12.5 (B1) 18.8 (B1) 25.0 (B1) 33.3 (B1) Current (A) 8.3 (B3) 12.5 (B3) 16.7 (B3) 22.2 (B3) 12/2 (B1) 10/2 (B1) 10/2 (B1) 8/2 (B1) Cable size 14/3 (B3) 14/3 (B3) 12/3 (B3) 10/3 (B3) Storage temperature 0-50°C / 32-122°F SAUNA STONES Size of stones Ø 5-10 cm / 2-4” Quantity of stones 20 kg / 44 lbs SAUNA ROOM 1900 mm / 75’’ (USA) Room height, min. 1980 mm / 78’’ (Canada) Floor area, min. 1 m2 / 10 ft2 1.5 m2 / 16 ft2 2.6 m2 / 28 ft2 3.7 m2 / 40 ft2 Floor area, max. 2 m2 / 20 ft2 2.8 m2 / 30 ft2 3.7 m2 / 40 ft2 6 m2 / 65 ft2 Room volume, min. 2.4 m3 / 84 ft3 2.8 m3 / 100 ft3 4.8 m3 / 170 ft3 7.1 m3 / 250 ft3 Room volume, max. 3.7 m3 / 130 ft3 6 m3 / 210 ft3 8.5 m3 / 300 ft3 12 m3 / 425 ft3"
    Limit: The manual gives current and cable size but no breaker rating; the electrician sizes the breaker to code.
  11. Harvia KIP KIP-60-B1: power, room volume and supply (240 V)
    Harvia KIP (built-in controls) instructions for installation and use, 5.3 Specifications. Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "KIP-30-B1/B3 KIP-45-B1/B3 KIP-60-B1/B3 KIP-80-B1/B3 Power (kW) 3.0 4.5 6.0 8.0 240 V 1 Phase (B1) Operating voltage 208 V 3 Phase (B3) Frequency (Hz) 50 / 60 12.5 (B1) 18.8 (B1) 25.0 (B1) 33.3 (B1) Current (A) 8.3 (B3) 12.5 (B3) 16.7 (B3) 22.2 (B3) 12/2 (B1) 10/2 (B1) 10/2 (B1) 8/2 (B1) Cable size 14/3 (B3) 14/3 (B3) 12/3 (B3) 10/3 (B3) Storage temperature 0-50°C / 32-122°F SAUNA STONES Size of stones Ø 5-10 cm / 2-4” Quantity of stones 20 kg / 44 lbs SAUNA ROOM 1900 mm / 75’’ (USA) Room height, min. 1980 mm / 78’’ (Canada) Floor area, min. 1 m2 / 10 ft2 1.5 m2 / 16 ft2 2.6 m2 / 28 ft2 3.7 m2 / 40 ft2 Floor area, max. 2 m2 / 20 ft2 2.8 m2 / 30 ft2 3.7 m2 / 40 ft2 6 m2 / 65 ft2 Room volume, min. 2.4 m3 / 84 ft3 2.8 m3 / 100 ft3 4.8 m3 / 170 ft3 7.1 m3 / 250 ft3 Room volume, max. 3.7 m3 / 130 ft3 6 m3 / 210 ft3 8.5 m3 / 300 ft3 12 m3 / 425 ft3"
    Limit: The manual gives current and cable size but no breaker rating; the electrician sizes the breaker to code.
    Another source disagrees: KIP60B: 169 to 300 cu ft, fuse min. 25 A, 10 AWG. Harvia US product page JC60B2401.
  12. Harvia KIP KIP-80-B1: power, room volume and supply (240 V)
    Harvia KIP (built-in controls) instructions for installation and use, 5.3 Specifications. Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "KIP-30-B1/B3 KIP-45-B1/B3 KIP-60-B1/B3 KIP-80-B1/B3 Power (kW) 3.0 4.5 6.0 8.0 240 V 1 Phase (B1) Operating voltage 208 V 3 Phase (B3) Frequency (Hz) 50 / 60 12.5 (B1) 18.8 (B1) 25.0 (B1) 33.3 (B1) Current (A) 8.3 (B3) 12.5 (B3) 16.7 (B3) 22.2 (B3) 12/2 (B1) 10/2 (B1) 10/2 (B1) 8/2 (B1) Cable size 14/3 (B3) 14/3 (B3) 12/3 (B3) 10/3 (B3) Storage temperature 0-50°C / 32-122°F SAUNA STONES Size of stones Ø 5-10 cm / 2-4” Quantity of stones 20 kg / 44 lbs SAUNA ROOM 1900 mm / 75’’ (USA) Room height, min. 1980 mm / 78’’ (Canada) Floor area, min. 1 m2 / 10 ft2 1.5 m2 / 16 ft2 2.6 m2 / 28 ft2 3.7 m2 / 40 ft2 Floor area, max. 2 m2 / 20 ft2 2.8 m2 / 30 ft2 3.7 m2 / 40 ft2 6 m2 / 65 ft2 Room volume, min. 2.4 m3 / 84 ft3 2.8 m3 / 100 ft3 4.8 m3 / 170 ft3 7.1 m3 / 250 ft3 Room volume, max. 3.7 m3 / 130 ft3 6 m3 / 210 ft3 8.5 m3 / 300 ft3 12 m3 / 425 ft3"
    Limit: The manual gives current and cable size but no breaker rating; the electrician sizes the breaker to code.
  13. Harvia KIP60B (JC60B2401): fuse and supply cable on the US product page
    Harvia US product page, KIP60B 6 kW 240VAC Steel UL (JC60B2401), technical data. Manufacturer page. Checked 22 Nov 2026, re-check by 22 May 2027.
    "Fuse (240VAC, 1 ph, 60Hz) pcs x ampers min. 25A / 2 group: min. 16,7A Supply cable (240VAC, 1ph, 60Hz) pcs x ampers 10AWG"
    Limit: A minimum fuse rating, not a full circuit specification; local code and the electrician decide the final breaker.
  14. Finnleo Designer 4.5 (1712-45-0207): power, room volume and wire (240 V, 1 phase)
    Finnleo Designer SL2 heater installation and operating instructions (72-0130), Diagram 2. Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "Heater 4.5 1 240 18.8 2 #10AWG+GR 2 #10AWG+GR 4.5 12 sq. ft. 74" 100 96" 210"
    Limit: Minimum volume is quoted at a 74 inch wall height and maximum at 96 inches; the chart gives no breaker size.
  15. Finnleo Designer 6.0 (1712-60-0207): power, room volume and wire (240 V, 1 phase)
    Finnleo Designer SL2 heater installation and operating instructions (72-0130), Diagram 2. Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "Heater 6.0 1 240 25 2 #10AWG+GR 2 #10AWG+GR 6.0 21 sq. ft. 74" 175 96" 310"
    Limit: Minimum volume is quoted at a 74 inch wall height and maximum at 96 inches; the chart gives no breaker size.
  16. Finnleo Designer 8.0 (1712-80-0207): power, room volume and wire (240 V, 1 phase)
    Finnleo Designer SL2 heater installation and operating instructions (72-0130), Diagram 2. Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "Heater 8.0 1 240 33.3 2 #8AWG+GR 2 #8AWG+GR 8.0 31 sq. ft. 74" 250 96" 425"
    Limit: Minimum volume is quoted at a 74 inch wall height and maximum at 96 inches; the chart gives no breaker size.
  17. Health Mate Enrich 2 infrared sauna: specifications
    Health Mate, Enrich 2 product page, Electrical and Dimensions. Manufacturer page. Checked 22 Nov 2026, re-check by 22 May 2027.
    "- 120V / 1780 Watts / 15 Amps - Electricity Calculator - Plugs into a standard 120V 15A outlet - Plug type: NEMA 5-15P Dimensions - Exterior: 47.25″W × 43.5″D × 77″H - Interior: 45″W × 39.5″D × 71.5″H"
    Limit: The heater and warranty details come from other sections of the same page, and lifetime coverage applies only to the heater core, harness and wiring.
  18. JNH Lifestyles Tosi 2 person infrared sauna: specifications
    JNH Lifestyles, Tosi 2 product page, Technical Specifications. Manufacturer page. Checked 22 Nov 2026, re-check by 22 May 2027.
    "**Exterior:** 47.3" (W) x 39.5" (D) x 75" (H) **Interior:** 45" (W) x 37" (D) x 72.5" (H) **Bench:** 42" (W) x 18.13" (D) 17.25" (Height from floor) **Door Opening:** 21.25" **Weight:** 330 lbs ### Electrical **Voltage:** 120V **Amperage:** 15 Amps **Power:** 1,540 Watts **Plug Type:** Standard Household Output"
    Limit: The heater counts and warranty come from other sections of the same page.
  19. Sunlighten Amplify II infrared sauna: specifications
    Sunlighten US shop, Amplify II product page, Specifications and dimensions. Manufacturer page. Checked 22 Nov 2026, re-check by 22 May 2027.
    "Exterior width 50.9" Exterior depth 45.9" Exterior height 77.7" (inc. 2" feet) Interior width 45.4" Interior depth 39.9" Interior height 70.3" Bench width 45.2" Bench depth 20.3" Bench height 19.5" from floor Door opening 28" Weight 541 lbs Heaters 5 FIR, 3 Full Spectrum Electrical 120V •1880W • 15.67A • NEMA 5-20R outlet"
    Limit: The warranty carries an asterisk for terms we did not capture, and the ETL wording is a brand-wide FAQ statement. Sunlighten's own spec sheet PDF gives a higher rating for the Amplify II, so the two Sunlighten documents disagree.
    Another source disagrees: 120 V, 2270 W, 18.92 A. Sunlighten Amplify II spec sheet (PDF).
  20. Clearlight Sanctuary 2 full spectrum infrared sauna: specifications
    Clearlight (infraredsauna.com), Sanctuary 2 product page, Specifications. Manufacturer page. Checked 22 Nov 2026, re-check by 22 May 2027.
    "120 Volts 2,260 Watts 18.83 Amps Plugs into a 120V / 20 Amp outlet. Plug: NEMA 5-20P"
    Limit: The page shows no price, and the dimensions and heater list are in other sections of the same page.
  21. NEC 2020 section 424.4(B): conductor size for fixed electric space-heating equipment
    "(B) Branch-Circuit Sizing. The branch-circuit conductors for fixed electric space-heating equipment and any associated motors shall be sized not smaller than 125 percent of the load."
    Limit: Article 424 does not name sauna heaters, so whether this rule applies to a sauna heater is for the local inspector; the rule covers conductors only, and later NEC editions renumber it.
  22. NEC 2020 section 210.20(A): breaker rating for continuous loads
    "(A) Continuous and Noncontinuous Loads. Where a branch circuit supplies continuous loads or any combination of continuous and noncontinuous loads, the rating of the overcurrent device shall not be less than the noncontinuous load plus 125 percent of the continuous load."
    Limit: The rule applies to continuous loads; the code text read here does not say a sauna heater is one, and an assembly listed for 100 percent operation is exempt.
  23. IRC 2024 section M1902.2: sauna heater installation and listing standard
    ICC International Residential Code 2024, section M1902.2. Standard. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "Sauna heaters shall be installed in accordance with the manufacturer’s instructions. Sauna heaters shall comply with UL 875."
    Limit: Applies only where this IRC edition is adopted; it does not name a certification body.
  24. IRC 2024 section M1902.4: sauna heater thermostat limit and sensor position
    ICC International Residential Code 2024, section M1902.4. Standard. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "Sauna heaters shall be equipped with a thermostat that will limit room temperature to not greater than 194°F (90°C). Where the thermostat is not an integral part of the heater, the heat-sensing element shall be located within 6 inches (152 mm) of the ceiling."
    Limit: A model code: it applies only where a jurisdiction has adopted this IRC edition, possibly with local amendments, and the 6 inch rule applies only to a sensor not built into the heater.
  25. UL 875 (10th edition, 2024) Electric Dry-Bath Heaters: scope and required controls
    "These requirements cover electric dry-bath heating equipment and other equipment rated 600 volts or less that is intended to produce a dry-heat environment to be installed in accordance with the National Electrical Code, ANSI/NFPA 70. [...] The completed equipment is to be provided with an automatic temperature-regulating control that may be integral with the heater or wall-mounted, with an integral manual-reset limit control, a timer, and any other necessary associated equipment."
    Limit: The scope says what a listed heater must include; it does not give the timer length or temperature limits, which sit in the paid standard.
  26. Electrical Safety Authority (Ontario) summary of OESC Rule 62-222: sauna heater timer
    Electrical Safety Authority and Ontario Fire Marshal, Flash 25-20-FL, May 2025. Regulator. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "Controlled by a timed cut-off switch having a maximum time setting of 1 hour, with no override feature that, if not forming part of the sauna heater or cabinet, will be mounted on the outside wall of the room containing the sauna heater and able to disconnect all ungrounded conductors in the circuit supplying the heater."
    Limit: This is ESA's summary of Ontario Electrical Safety Code Rule 62-222, not the code text, and Ontario's code can differ from the CSA C22.1 code adopted elsewhere in Canada.
  27. Electrical Safety Authority (Ontario) summary of OESC Rule 62-112: temperature limit for nearby combustibles
    Electrical Safety Authority and Ontario Fire Marshal, Flash 25-20-FL, May 2025. Regulator. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "Rule 62-112 requires that heating devices are to be installed so that any adjacent combustible materials are not subjected to temperatures in excess of 90° C."
    Limit: ESA's summary of a general heating rule in the Ontario code, not the code text, and not a sauna room air temperature limit.
  28. HUUM US manuals: GFCI breaker
    HUUM DROP US manual (H1001L08 v8), Connecting the heater to the power supply. Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "It is recommended to connect the unit to the mains without a GFCI breaker."
    Limit: A maker recommendation; local electrical code may still require ground fault protection.
  29. Harvia Cilindro US manual: RCD or GFI
    Harvia Cilindro Owner's / Operator's Manual USA, 3.7 Electric heater insulation resistance. Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "Do not connect the power feed for the heater through the RCD (residual current device)/GFI (Ground Fault Interrupter)!"
    Limit: Local code can override a maker instruction; the electrician decides.
  30. Harvia KIP US manual: breaker type
    "NOTE: The heater must be connected to a standard 2-pole breaker. Do not use a ground fault circuit interrupter (GFCI)."
    Limit: States the breaker type but not its amp rating.
  31. Finnleo Designer SL2 manual: GFCI
    Finnleo Designer SL2 heater installation and operating instructions (72-0130), wiring diagram notes. Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "NOTE: A GFCI (Ground Fault Interrupt Circuit) device is not required by NEC. A GFCI may be installed if required by local codes but will nuisance trip during use of the product."
    Limit: Finnleo's reading of the NEC, not an inspector's ruling.
  32. HUUM US manuals: who does the electrical work
    HUUM DROP US manual (H1001L08 v8), page 3. Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "ATTENTION! The following instructions for electrical works must be carried out by a licensed electrician."
    Limit: The manual later says "certified electrician" for connecting power; it does not define either term.
  33. Harvia Cilindro US manual: electrical connection
    Harvia Cilindro Owner's / Operator's Manual USA, 3.5 Electrical Connections. Manufacturer manual. Checked 22 Nov 2026, re-check by 22 Nov 2027.
    "The heater may only be connected to the electrical network in accordance with the current regulations by an authorised, licensed professional electrician."
    Limit: The 90 °C wire rule is in a later sentence of the same section.
  34. Finnleo Designer SL2 manual: electrical hook-up
    "Electrical installation must be made by a licensed electrician in accordance with the National Electrical Code and local regulations."
    Limit: States who installs, not what the circuit must be.
  35. HUUM warranty: licensed electrician and proof
    HUUM Limited Warranty Terms and Conditions v4 (linked from huumsauna.com/warranty). Manufacturer page. Checked 22 Nov 2026, re-check by 22 May 2027.
    "3.4. The electrical product is installed and connected to the electrical network by a licensed, professional electrician and proof of this is presented to HUUM."
    Limit: Does not say what form of proof HUUM accepts.
  36. Supply that 1 and 2 person plug-in infrared cabins are sold for
    Heavenly Heat guide to plug-in infrared saunas. Seller page. Checked 22 Nov 2026, re-check by 22 May 2027.
    "Most 1- and 2-person plug-in infrared saunas are built to operate on a standard 120V, 15-amp, three-prong household outlet. [...] Slightly larger models, such as the GSE-2, GSE-3, GSE-3C, and GSE-4, usually require a dedicated 110-volt outlet rated for 20 amps."
    Limit: One seller describing the category, not a nameplate. The page gives three wattage ranges that do not agree with each other.
  37. Sunlighten Amplify II: heaters and supply
    Sunlighten Amplify II spec sheet (Doc 09142026). Manufacturer manual. Checked 22 Nov 2026, re-check by 22 May 2027.
    "Floor/Roof/Hardware/Bench:13”Wx51”D x56”H Heaters:5 FIR, 3 FS Walls:14”Wx51”D x76”H *Amplify models do not have a floor heater. E L E C T R I C A L P A N E L S Electrical:120V 2270W18.92A Roofpanel:51”Wx45.9”D x3”T Dedicated 120V 20A circuit required"
    Limit: Read from a two-column PDF as text, so carton and panel sizes run into the same lines; the sheet gives no per-heater wattage.
    Another source disagrees: 120 V at 1,880 W and 15.67 A. Sunlighten Amplify II product page (shop-us).